Preventing Overheating with a
High-capacity Heat Sink (Y92B-P250NF)
? When the High-capacity Heat Sink is used, high-capacity switching
at 75 A or 90 A requires forced cooling with a fan. Connect the Fan
to a power supply according to its ratings specifications.
? If the Fan stops due to a power supply error, due to foreign matter
in the power supply connection, or due to aging, the Heat Sink will
heat to high temperatures, possibly resulting in failure of the SSR or
adverse affects on other devices. Implement an overheating pre-
vention measure, such as turning OFF the load current, if the Heat
Sink overheats.
? A thermostat is provided to detect overheating. The thermostat uses a
NC contact, i.e., the circuit will be opened for overheating. This thermo-
stat can be used to stop the operation of the SSR. Implement an over-
heating prevention measure by using this signal to output an alarm or
perform another response applicable to the system. Also, confirm that
there is no problem with the overall system.
? Do not connect the thermostat directly to the load power supply.
Connect it to a contactor or other shutoff device connected above
the SSR.
? Terminals equivalent to Faston #187 are used for the thermostat
terminals.
? Do not place heat-dissipating silicon grease on the thermostat.
? Do not solder the thermostat terminals.
? The following diagram shows a protective circuit example.
Circ u it breaker
2. DC-switching models
Less than 3 m
Load
Input G3 N A-UTU Output
? The input cable must be less than 3 m.
Loss Time
The loss time will increase when the G3NA is used at a low applied
voltage or current. Be sure that this does not cause any problems.
Loss time
Using DC Loads
For a DC or L load, a diode should be connected in parallel the load
to absorb the counter electromotive force of the load.
Coil
Circ u it breaker
(coil side)
Thermostat
(NC contact)
Y92B-P250NF
Load
(contact side)
Inp u t
SSR
Load
Load po w er
s u pply
po w er
s u pply
G3NA
Load side
Inp u t side
Ventilating a High-capacity Heat Sink
(Y92B-P250NF)
Circ u it
breaker
Fuses
Connect a quick-break fuse in series with the load as a short-circuit
protection measure. Use one of the fuses in the following table or one
with equivalent or better characteristics.
Recommended Fuses
60LFF8
G3NA-210B
? Refer to Ventilation Outside the Control Panel .
Operating Conditions
? Do not apply currents exceeding the rated current otherwise, the
temperature of the G3NA may rise excessively.
? As protection against accidents due to short-circuiting, be sure to
G3NA rated
load current
5A
8A
10 A
Fuse model Manufacturer Applicable SSR
60LFF5 Hinode Electric G3NA-205B
Co., LTD.
60LFF10
install protective devices, such as fuses and no-fuse breakers, on
the power supply side.
? Do not apply overvoltages to the input circuit or output circuit. Fail-
ure or burning may result.
? Do not drop the G3NA or otherwise subject it to abnormal shock.
Malfunction or failure may result.
? Keep the cooling system running continuously during the ON/OFF
operation of the SSR. This is to allow residual heat to dissipate
while the SSR is OFF. (load current 75A, 90A models)
EMC Directive Compliance (For -UTU type)
EMC directives can be complied with under the following conditions.
1. AC-switching models
? A capacitor must be connected to the input power supply.
15 A
20 A
25 A
30 A
40 A
45 A
50 A
75 A
80 A
100 A
60LFF15
60LFF20
50SHA20
60PFF25
50SHA25
60PFF30
50SHA30
50SHA40
50SHA45
50SHA50
50SHA75
50SHA80
50SHB100
G3NA-220B
G3NA-240B
G3NA-275B-UTU-2
G3NA-290B-UTU-2
? A capacitor, varistor and toroidal core must be connected to the
load power supply.
? The input cable must be less than 3 m.
Troidal core
Load
Reverse Connection
The output terminal side of the G3NA-D210B is connected to a built-
in diode to protect the SSR from damage that may result from
reverse connection. The SSR, however, cannot withstand one minute
or more if the wires are connected in reverse. Therefore, pay the
Input
G3 N A
Output
utmost attention not to make polarity mistakes on the load side.
3 m max.
Recommended Capacitor : 0.05 μ F, 500 V AC (Load)
0.1 μ F, 250 V AC (Input)
Recommended V aristor : 470 V , 1750 A
Recommended Troidal core : N EC/TOKI N :ESD-R-25B or equi v alent
Solid State Relay
G3NA
483
相关PDF资料
ZXSC310EV BOARD EVALUATION FOR ZXSC310E5TA
000-16300 CONN PLUG BNC RG-180B/U
000-36800 CONN JACK BNC STR CRIMP RG58,141
000-53175 CONN PLUG 7/8 TRIAX 21-529 CABLE
000-79875 CONN PLUG TNC CLAMP STR 58/U
000-86350 CONN JACK BNC BULKHD RG174 188
0001.1001.TR FUSE 500MA 250V 5X20 FAST CERM
0001.1006 FUSE 1.6A 250V 5X20 FAST CERM
相关代理商/技术参数
Y92BN100 制造商:OMRON AUTOMATION AND SAFETY 功能描述:HEAT SINK TRACK MNT FOR G3NA SER 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:Solid State Relay, Heat Sinks
Y92B-N100 功能描述:散热片 TRK MT HEAT SINK G3N RoHS:否 制造商:Ampro By ADLINK 产品:Heat Sink Accessories 安装风格:Through Hole 散热片材料: 散热片样式: 热阻: 长度: 宽度: 高度: 设计目的:Express-HRR
Y92BN150 制造商:OMRON AUTOMATION AND SAFETY 功能描述:HEAT SINK TRACK MNT FOR G3NA SER 制造商:Omron Electronic Components LLC 功能描述:Heat Sink Passive Screw 1.38|C/W 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:Heat Sink Passive Screw 1.38°C/W
Y92B-N150 功能描述:散热片 TRK MT HEAT SINK G3N RoHS:否 制造商:Ampro By ADLINK 产品:Heat Sink Accessories 安装风格:Through Hole 散热片材料: 散热片样式: 热阻: 长度: 宽度: 高度: 设计目的:Express-HRR
Y92BN50 制造商:OMRON AUTOMATION AND SAFETY 功能描述:HEAT SINK TRACK MNT FOR G3NA SER 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:Solid State Relay, Heat Sinks
Y92B-N50 功能描述:散热片 TRK MT HEAT SINK G3N RoHS:否 制造商:Ampro By ADLINK 产品:Heat Sink Accessories 安装风格:Through Hole 散热片材料: 散热片样式: 热阻: 长度: 宽度: 高度: 设计目的:Express-HRR
Y92BN50V 制造商:Omron Corporation 功能描述:
Y92BP100 制造商:OMRON AUTOMATION AND SAFETY 功能描述:HEAT SINK 1.01C/W 450G FOR G3PB 制造商:OMRON INDUSTRIAL AUTOMATION 功能描述:Heat Sink Passive 1.01°C/W